800-624-3393

  •    Downloads

MRP Vessel Chiller RVS distributed by Clark Johnson Co

Vessels

MRP Recirculator Systems

 

MRP Recirculator Systems are completely assembled by a factory-trained workforce dedicated to building quality refrigeration products.  All packages, vessels and piping are fabricated from ASME Code materials by certified welders.  The packages are assembled in a controlled factory environment to the industry’s highest quality standards.  The finished package is designed for long-life, simplified installation, and easy access to perform routine maintenance functions

 

The new MRP Recirculator System utilizes the highest quality and most advanced components available in the refrigeration industry today.  At the heart of the MRP Recirculator System is the Matrix Microprocessor Panel. The Matrix Microprocessor Panel has been engineered to provide total recirculator control including proportional liquid feed and level control, pump

protection and a state of the art by-pass flow control (patent pending) to improve pump efficiency and capacity.  The standard MRP Recirculator System features Teikoku hermetic pumps with exclusive bearing wear monitor and secondary containment system to eliminate the possibility of a refrigerant release.  The MRP Recirculator System is available in a complete range of

vessel diameters from 24” to 144”, in both vertical and horizontal

configurations.

 

Matrix Microprocessor Panel

The RVS Matrix Microprocessor Panel utilizes the latest technology to provide a total control solution for the MRP Recirculator System.  The Matrix Panel features a NEMA-4 enclosure and is UL/cUL listed.  The standard MRP Recirculator incorporates a Matrix Microprocessor Panel with starters, disconnects and power transformer requiring only a single power

connection in the field.  Factory packaging assures a completely tested andfunctional unit, ready-to-go without expensive field wiring and complicatedPLC programming, for simplified installation and start-up.

 

Minimum Pump Flow Control

  • Matrix detects low pump flow and automatically opens
  • minimum flow bypass valve
  • Eliminates the requirement for oversizing pump and
  • motor to accommodate minimum flow requirement
  • Integrated Pump Control
  • Automatic operation of up to 3 pumps
  • Pump differential pressure monitoring and safety
  • cutouts
  • Motor current monitoring and safety cutouts

Liquid Level Management

  • Reads 4-20mA signal from level probe and provides digital readout on panel
  • Automatic operation of proportional liquid
  • feed valves or solenoid valves
  • High and low level alarms
  • High and low level cutouts
  • Startup mode to provide additional liquid
  • ballast for on/off process operations

Communications and Data Logging

  • Industry standard protocol MODBUS over
  • RS-485 or Ethernet
  • Capable of remote and local monitoring
  • and control of system parameters
  • Monitored conditions logged and saved in
  • the event of a failure

Operator Interface

  • User friendly with large easy to read graphic display
  • Simple keypad screen navigation and set-point entry
rvs distributed by clark johnson co